{"support":{"yesButton":"Yes","noButton":"No","feedback":{"title":"What can we do to improve?"},"submitButton":"Submit","successMessage":"Thank you for your feedback","title":"Did this answer your question?","feedbackPercentLabel":"of people found this helpful","captcha":{"error":"Please check the box"}}}
Search FAQs

[Restriction]  GP-Pro EX/ Siemens AG TIA Portal Ethernet Driver

Symptom:
In case of using the S7-1200 series, the communication does not work with firmware version 4.7.0.
In case of using the S7-1500 series, the communication does not work with firmware version 4.0.(connection not confirmed)

S7-1200 G2 series cannot be used.

Cause:
Communication is not possible with displays that do not support secure communication.

NOTE:

Secure communication is supported by the GP6000 series and IPC series (PC/AT, PS5000/6000 series).
Currently confirmed secure communication-only devices: (GP-Pro EX 5.01+ GP6000 series and IPC series can be connected)

Solution:
1. Please use a firmware version lower.

2. Only SIMATIC S7-1200 series firmware version 4.7.3 supports non-secure communication, so it can be used with all displays that support the TIA Portal driver (GP4000/SP5000/ST6000).