SRT10KXLI

APC-LEAN-9J7K3Y_01

APC Smart-UPS On-Line, 10kVA/10kW, Tower, 230V/400V, 6x C13+4x C19 IEC outlets, Network Card+SmartSlot, Extended runtime, W/O rail kit

Overview
Presentation
High density, double-conversion on-line power protection with scalable runtime.
Main
Main Input Voltage
230 V AC 1 phase
380 V AC 3 phases
400 V AC 3 phases
415 V AC 3 phases
Input voltage
220 V
240 V
380 V
415 V
Input voltage limits
100...275 V adjustable (half load)
173...476 V adjustable (half load)
Number of input connectors
1 hard wire 3-wire (1P + N + E)
1 hard wire 5-wire (3P + N + E)
Network frequency
40...70 Hz auto-sensing
Output voltage
230 V 1 phase
Output voltage
220 V
240 V
Rated power in W
10000 W
Rated power in VA
10000 VA
Output connection type
6 IEC 60320
3 IEC Jumpers
4 IEC 60320
Output connector type
Hard wire 3-wire (H N + E) for 1 zone(s)
Bypass type
Internal bypass (automatic and manual)
Crest factor
3 : 1
Harmonic distortion
Less than 2 %
Maximum configurable power in VA
10000 VA
Maximum configurable power in W
10000 W
UPS type
On-Line
Wave type
Sine wave
Output frequency
50/60 Hz +/- 3 Hz sync to mains
Complementary
Battery type
Lead-acid internal included
Emergency power off
Yes
Free slots
1
Preinstalled device
Network management card 3 with environmental monitoring
Alarm
Audible and visible alarms : prioritized by severity
UPS connectivity
Serial port
USB port
Embedded network management card 3
Available expansion slot
Surge energy rate
480 J
Colour
Black
Width
263 mm
Height
432 mm
Depth
715 mm
Net weight
111.82 kg
Mounting location
Front
Mounting preference
No preference
Mounting mode
Rack-mounted with kit
USB compatible
Yes
Mounting mode
Tower with included kit
Provided equipment
CD with software
Documentation CD
Installation guide
Temperature probe
USB cable
Warranty card
Web/SNMP management card
Additional specification
High density
Redundant
No
Product or component type
Uninterruptible power supply (UPS)
Range of product
Smart-UPS On-Line
Curve equation
Efficiency
Curve fixed loss
0.0093
Curve load maximum
100 %
Curve load minimum
1 %
Curve proportional loss
0.0195
Curve square loss
0.0278
Curve test cond ID
Curve fit of data measured in accordance with the ENERGY STAR Test Method for Uninterruptible Power Supplies. All measurements taken in normal mode(s), at typical environmental conditions, with 230V/50Hz electrical input and balanced resistive load (PF = 1.0) output.
Curve X-axis maximum
100 %
Curve X-axis minimum
0 %
Curve X-axis title
Load
Curve X-axis units
Percentage
Curve Y-axis maximum
100 %
Curve Y-axis minimum
50 %
Curve Y-axis title
Efficiency
Curve Y-axis units
Percentage
Graph display
1
Show note OP temperature
No
UPS size
S
Environment
Product certifications
CE
EAC
IRAM
RCM
VDE
Marking
CE Mark
Standards
EN/IEC 62040-1:2019/A11:2021
EN/IEC 62040-2:2006/AC:2006
EN/IEC 62040-2:2018
Ambient air temperature for operation
0…40 °C
Ambient air temperature for storage
-15…45 °C
Storage altitude
0…15240 m
IP degree of protection
IP20
Relative humidity
0…95 %
Storage Relative Humidity
0…95 % non-condensing
Acoustic level
55 dBA
Heat dissipation
1947 Btu/h
Operating altitude
0...10000 ft
Batteries & Runtime
Battery type
Lead-acid battery
Battery voltage
+/- 192 V (split battery referenced to neutral)
Extended runtime
1
Battery recharge time
1.5 h
Number of battery replacement quantity
2
Battery life
3…5 year(s)
Battery charger power
876 W rated
Battery curve
D
Battery design life
2 year(s)
UPS design life
7 year(s)
Battery power in VAH
1805 VAh runtime
Battery option
SRT192BP2 1 3610 VAh
SRT192BP2 2 5415 VAh
SRT192BP2 3 7220 VAh
SRT192BP2 4 9025 VAh
SRT192BP2 5 10830 VAh
SRT192BP2 6 12635 VAh
SRT192BP2 7 14440 VAh
SRT192BP2 8 16245 VAh
SRT192BP2 9 18050 VAh
SRT192BP2 10 19855 VAh
General
Number of tare power
65 W
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
46.100 cm
Package 1 Width
100.000 cm
Package 1 Length
60.000 cm
Package 1 Weight
126.820 kg
Contractual warranty
Warranty (in months)
36 UPS|24 Battery

Offer SustainabilityOffer Sustainability

Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.

Environmental Data Explained
Recyclability potential, in %
65
Total lifecycle Carbon footprint
21 597 kg CO2 eq.
Carbon footprint of the manufacturing phase [A1 to A3]
1 613 kg CO2 eq.
Carbon footprint of the distribution phase [A4]
18 kg CO2 eq.
Carbon footprint of the installation phase [A5]
0 kg CO2 eq.
Carbon footprint of the use phase [B2, B3, B4, B6]
19950.0050218753
Carbon footprint of the use phase [B2, B3, B4, B6]
19 950 kg CO2 eq.
Sustainable packaging
No
Carbon footprint of the end-of-life phase [C1 to C4]
15.7370847508
Carbon footprint of the end-of-life phase [C1 to C4]
16 kg CO2 eq.
Environmental Disclosure
Total lifecycle Carbon footprint
21597
Average percentage of recycled plastic content
15 %
Packaging made with recycled cardboard
Yes
Packaging without single use plastic
No
SCIP Number
409c68a1-39a6-4e5f-b080-12befe783ad8
California proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Removable battery
User replaceable
Take-back
No
WEEE Label
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
ページトップに戻るページトップに戻る