SRT1000XLI

SPD_JVAN-BBRPD6_FL_H

APC Smart-UPS On-Line, 1000VA/1000W, Tower, 230V, 6x C13 IEC outlets, SmartSlot, Extended runtime, W/O rail kit

Overview
Presentation
High density, double-conversion on-line power protection with scalable runtime.
Main
Main Input Voltage
230 V AC 1 phase
Input voltage
220 V
240 V
Input Connection Type
IEC 60320 C14
Input voltage limits
100...275 V 40% load
176...275 V full load
Network frequency
40...70 Hz auto-sensing
Output voltage
230 V AC 1 phase
Output voltage
220 V
240 V
Rated power in W
1000 W
Rated power in VA
1000 VA
Output connection type
6 IEC 60320
Bypass type
Built-in bypass
Crest factor
3 : 1
Harmonic distortion
Less than 2 %
Maximum configurable power in VA
1000 VA
Maximum configurable power in W
1000 W
UPS type
On-Line
Wave type
Sine wave
Output frequency
50/60 Hz +/- 3 Hz sync to mains
Complementary
Battery type
Lead-acid internal included
Emergency power off
Yes
Free slots
1
Alarm
Audible and visible alarms : prioritized by severity
UPS connectivity
Serial port
USB port
Surge energy rate
432 J
Cable length
1.8 m
Number of cables
1
Colour
Black
Width
85 mm
Height
432 mm
Depth
505 mm
Net weight
20.5 kg
Mounting location
Front
Mounting preference
No preference
Mounting mode
Tower
USB compatible
Yes
Mounting position
Vertical
Mounting mode
Tower
Provided equipment
CD with software
Communication cable
Documentation CD
Installation guide
Removable support feet
USB cable
Warranty card
Additional specification
High density
Redundant
No
Product or component type
Uninterruptible power supply (UPS)
Range of product
Smart-UPS On-Line
Curve equation
Efficiency
Curve fixed loss
0.0378
Curve load maximum
100 %
Curve load minimum
4 %
Curve proportional loss
0.0216
Curve square loss
0.022
Curve test cond ID
Curve fit of data measured in accordance with the ENERGY STAR Test Method for Uninterruptible Power Supplies. All measurements taken in normal mode(s), at typical environmental conditions, with 230V/50Hz electrical input and balanced resistive load (PF = 1.0) output.
Curve X-axis maximum
100 %
Curve X-axis minimum
0 %
Curve X-axis title
Load
Curve X-axis units
Percentage
Curve Y-axis maximum
100 %
Curve Y-axis minimum
50 %
Curve Y-axis title
Efficiency
Curve Y-axis units
Percentage
Graph display
1
Show note OP temperature
No
UPS size
S
Environment
Product certifications
CE
EAC
UK PSTI
Marking
CE Mark
Standards
EN/IEC 62040-1:2019/A11:2021
EN/IEC 62040-2:2006/AC:2006
EN/IEC 62040-2:2018
Ambient air temperature for operation
0…40 °C
Ambient air temperature for storage
-20…50 °C
Storage altitude
0…15240 m
IP degree of protection
IP20
Relative humidity
0…95 % non-condensing
Storage Relative Humidity
0…95 % non-condensing
Acoustic level
50 dBA
Heat dissipation
317 Btu/h
Operating altitude
0...10000 ft
Batteries & Runtime
Battery type
Lead-acid battery
Battery voltage
48 V
Extended runtime
1
Number of battery filled slots
1
Battery recharge time
3 h
Number of battery replacement quantity
1
Battery life
3…5 year(s)
Battery charger power
97 W rated
Battery curve
D
Battery design life
2 year(s)
UPS design life
7 year(s)
Battery power in VAH
293 VAh runtime
Battery option
SRT48BP 1 879 VAh
SRT48BP 2 1465 VAh
SRT48BP 3 2051 VAh
SRT48BP 4 2637 VAh
SRT48BP 5 3223 VAh
SRT48BP 6 3809 VAh
SRT48BP 7 4453 VAh
SRT48BP 8 4981 VAh
SRT48BP 9 5641 VAh
SRT48BP 10 6153 VAh
General
Number of tare power
16 W
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
24.5 cm
Package 1 Width
69 cm
Package 1 Length
59.5 cm
Package 1 Weight
32.58 kg
Contractual warranty
Warranty (in months)
36 UPS|24 Battery

Offer SustainabilityOffer Sustainability

Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.

Environmental Data Explained
Recyclability potential, in %
65
Total lifecycle Carbon footprint
3 372 kg CO2 eq.
Carbon footprint of the manufacturing phase [A1 to A3]
359 kg CO2 eq.
Carbon footprint of the distribution phase [A4]
4 kg CO2 eq.
Carbon footprint of the installation phase [A5]
0 kg CO2 eq.
Carbon footprint of the use phase [B2, B3, B4, B6]
3004.9448996834
Carbon footprint of the use phase [B2, B3, B4, B6]
3 005 kg CO2 eq.
Mercury free
Yes
Sustainable packaging
No
Carbon footprint of the end-of-life phase [C1 to C4]
3.5042599385
Carbon footprint of the end-of-life phase [C1 to C4]
4 kg CO2 eq.
Environmental Disclosure
Total lifecycle Carbon footprint
3372
Average percentage of recycled plastic content
15 %
Packaging made with recycled cardboard
Yes
Packaging without single use plastic
No
SCIP Number
B2b22a56-41f2-497e-9ea6-cf093b3b8bd3
Removable battery
User replaceable
Take-back
No
WEEE Label
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
ページトップに戻るページトップに戻る