BVX900LI-MS

Easy_UPS_BVX700LI_Image_FR_H

APC Easy UPS, 900VA, Tower, 230V, 2 Universal + 1 IEC C13 outlets, AVR

Main
Main Input Voltage
230 V AC 1 phase
Input Connection Type
IEC 60320 C14
Cos phi
0.53
Input voltage limits
140...300 V 230 V AC
Network frequency
50/60 Hz +/- 5 Hz auto-sensing
Output voltage
230 V AC 1 phase
Rated power in W
480 W
Rated power in VA
900 VA
Output connection type
2 universal
1 IEC 60320 C13
Type of USB power supply
None
Maximum configurable power in VA
900 VA
Maximum configurable power in W
480 W
Transfer time
6 ms typical : 10 ms maximum
UPS type
Line interactive
Wave type
Stepped approximation to a sinewave
Full load runtime
00:01:00 480 W
Half load runtime
00:06:30 240 W
Output frequency
50/60 Hz +/- 1 Hz sync to mains
Complementary
Battery capacity
9.0 Ah
Battery type
Lead-acid internal included
Control panel
LED Status display with on line : on battery
Surge energy rate
273 J
Cable length
1.2 m
Number of cables
1
Colour
Black
Width
120 mm
Height
160 mm
Depth
355 mm
Net weight
6 kg
Mounting support
Floor
Mounting preference
No preference
Mounting mode
Not rack-mountable
USB compatible
No
Mounting mode
Desktop installation compact
Provided equipment
User manual
Max runtime
120 min
Redundant
No
Product or component type
Uninterruptible power supply (UPS)
Range of product
Easy UPS
Curve equation
Efficiency
Curve fixed loss
0.0284
Curve load maximum
100 %
Curve load minimum
3 %
Curve square loss
0.0028
Curve test cond ID
Curve fit of data measured in accordance with the ENERGY STAR Test Method for Uninterruptible Power Supplies. All measurements taken in normal mode(s), at typical environmental conditions, with 230V/50Hz electrical input and balanced resistive load (PF = 1.0) output.
Curve X-axis maximum
100 %
Curve X-axis minimum
0 %
Curve X-axis title
Load
Curve X-axis units
Percentage
Curve Y-axis maximum
100 %
Curve Y-axis minimum
50 %
Curve Y-axis title
Efficiency
Curve Y-axis units
Percentage
Graph display
1
Show note OP temperature
No
UPS size
WS
Environment
Product certifications
CE
Standards
EN/IEC 62040-1:2019/A11:2021
EN/IEC 62040-2:2006/AC:2006
EN/IEC 62040-2:2018
Ambient air temperature for operation
0…40 °C
Ambient air temperature for storage
-15…40 °C
Storage altitude
0…3000 m
IP degree of protection
IP20
Relative humidity
0…95 % non-condensing
Storage Relative Humidity
0…95 % non-condensing
Acoustic level
40 dBA
Operating altitude
0...3000 m
Batteries & Runtime
Battery type
Lead-acid battery
Battery voltage
12 V
Battery graph comments
Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output.
Battery recharge time
8 h
Battery life
2…3 year(s)
Battery curve
B
Battery power in VAH
97 VAh runtime
108 VAh capacity
General
Number of tare power
28 W
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
25 cm
Package 1 Width
43 cm
Package 1 Length
19.7 cm
Package 1 Weight
6.5 kg
SCC14
10731304404368
Contractual warranty
Warranty (in months)
24

Offer SustainabilityOffer Sustainability

Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.

Environmental Data Explained
Toxic heavy metal free
Yes
Mercury free
Yes
Sustainable packaging
No
Environmental Disclosure
Packaging made with recycled cardboard
Yes
Packaging without single use plastic
No
SCIP Number
E7333b0a-8d2c-4a40-a279-6eb5db3419eb
End of life manual availability
Removable battery
No
Take-back
No
ページトップに戻るページトップに戻る