Unrecoverable Errors
|
Error Message |
Cause and Troubleshooting |
|
Detected an unrecoverable error. To recover, touch Reset or restart the display unit. |
Touch [Reset] and restart the display unit. If restarting does not resolve the error, contact customer support. |
When the display unit's internal system will not start correctly
When there is a problem with the files related to starting the system, the following error messages will be displayed on the forced transfer screen. Transfer the system data again with the transfer tools.
![]()
For details about the transfer tools, please see 34.12.1 Transfer Settings Guide.
|
Error Message |
Cause and Troubleshooting |
|
Start up Error: Boot.cfg |
Boot.cfg file, needed for startup, is deleted or damaged. Try a forced transfer of the project file. |
|
Start up Error: Default Font |
Default font data is deleted or damaged. Try a forced transfer of the project file. |
|
Start up Error: LanSys.cfg |
LAN settings file is damaged. Try a forced transfer of the project file. |
|
Start up Error: System.cfg |
Files needed to start the system (system settings files) do not exist. Try a forced transfer of the project file. |
|
Start up Error: SD memory loader |
Abnormal Boot.cfg file data in the SD card during startup. Replace the data on the SD card. |
|
Start up Error: SD MOUNT Error |
Failed to read SD card during SD card startup. Try loading again by changing the SD card or by another method. |
|
Start up Error: Runtime Load NG |
GP internal system data is deleted or damaged Try a forced transfer of the project file. |
|
Start up Error: Runtime Start NG |
The following error may have occurred during runtime startup. Try a forced transfer of the project file.
|
|
Compulsion Transfer Mode |
Forced transfer display that appears when touching the bottom-left or bottom-right part of the screen at startup. *1 |
*1This item does not indicate an error and is a screen that displays normally.
When the display unit's internal system will not start properly (when using GP-4201TM, or GP-4301TM)
When there is a problem with the files needed after the system starts up, the following error messages will be displayed on the normal transfer screen. After fixing the problem, transfer the files again with the transfer tools.
![]()
For details about the transfer tools, please see 34.11 Installing Only the Transfer Tool.
|
Error Message |
Cause and Troubleshooting |
Browse |
|
Cannot read the file ( **** ) required for startup. Please transfer the project data again. |
A file needed for startup could not be read. Transfer again and restore the system. The file name displayed inside the brackets is either abnormal or does not exist. |
- |
|
An illegal or undetermined Device Address exists ( ***** ). Please check the settings and transfer the project data again. |
Appears when the device address used by a part or function is invalid. The part or function name using the invalid address is displayed in the brackets. However, sometimes the brackets are not displayed. Edit the device address, and transfer again to recover. |
|
|
The number of devices/PLCs exceeds the maximum setting. Please check the settings then transfer the project again. |
The number of devices/PLCs exceeds the maximum setting. (Large-scale models: 4, medium-scale models: 2) Reconfirm the project settings and transfer again. |
|
|
Unable to open I/O Driver with this Runtime version. |
The I/O driver version is out of date. Check the runtime version, and transfer an I/O driver of a compatible version again. |
- |
When an abnormal file is detected during startup (For SP5000 series)
|
Error Message |
Cause and Troubleshooting |
Browse |
|
Cannot read the file required for startup. Reset and transfer the project again. |
A file needed for startup could not be read. System information in the system card is not correct. Reset and transfer the project data again. |
- |
|
System Card is missing. The system card is not inserted. |
Insert the system card and restart the display unit.
|
- |
|
System Card is write-protected. |
Cancel the write protection. |
- |
|
Security data is invalid. Reset and transfer the project again. |
The security information is not correct. Reset and transfer the project data again. |
- |
|
Invalid password. Too many attempts. Reset and transfer the project again. |
Incorrect passwords or user IDs were entered 5 times. Reset and transfer the project data again. |
- |
When an abnormal file is detected during startup (For GP6000, GPH6000, ST6000 2nd Gen series)
|
Error Message |
Cause and Troubleshooting |
Browse |
|
The project data is invalid. (Transfer the project again.) |
A file needed for startup could not be read. |
|
When an abnormal connection key is detected during the display unit’s startup
If an error is detected in the connection key setting during system startup, the following error message will display.
|
Error Message |
Cause and Troubleshooting |
Browse |
|
Connection key has not been set up. Use the memory loader to restore. |
The connection key has not been set up properly. Use the Memory Loader to transfer the project file again. Transferring with the Transfer Tool will not resolve this error. |
Errors displayed in offline mode
When creating a recipe (CSV data) index file
|
Error Message |
Cause and Troubleshooting |
Browse |
|
CF/SD Card is missing. |
Cannot recognize the SD Card. 1. Correctly insert the SD Card into the SD Card slot on the display unit. 2. Make sure that the SD Card has been formatted using a file format compatible with the display unit. |
|
|
USB storage is missing. |
Cannot recognize the USB storage. 1. Connect the USB storage to the display unit. 2. Make sure that the USB storage has been formatted using a file format compatible with the display unit. |
|
|
CSV file is missing. |
The FILE folder does not exist or there is no CSV data file in the folder. Or, there are CSV files but they are invalid for CSV transfer. Save the CSV data files onto external storage and try the transfer again. If an index file already exists, the original file will remain. |
|
|
Failed to write to file. |
The external storage is faulty or the index file is read-only. Use external storage which can read and write properly. If the index file is read-only, unprotect it and try writing again. |
While performing [Transfer from SD to SRAM]
|
Error Message |
Cause and Troubleshooting |
Browse |
|
This is a file of a different size from the SRAM size of the unit. |
The file size for the backup data transferred from the SD Card differs from the size of the backup memory (SRAM) used by the display unit. Transfer the backup data of the same size. |
- |
|
It is created with a model of a different data format or of a different version. |
The backup data created with a model having no data compatibility is transferred to the backup memory (SRAM). Transfer compatible backup data. |