OMRON Corporation C/CV Series HOST Link |  | | To change a cable (RS-232C) used with the GP2000/77R/70 series to one for the GP3000 series | | Connect the cable to COM1. | | ◆ | System configuration diagram of the GP2000/77R/70 series | |  | | | ◆ | System configuration diagram of the GP3000 series | | | | | Important notes for the replacement of a cable from the GP2000/77R/70 series to the GP3000 series * Read carefully. | | For replacing hardware from the GP2000/77R/70 series to the GP3000 series, read the following notes: | | Supported devices | - | In GP-Pro EX, the notations of word devices and nodes differ. | | In GP-Pro EX, the bit data of word device is hexadecimal. The word address and the bit address are separated by a dot. GP-Pro/PB3 | GP‐PRO EX | DM000015 | DM0000.15 | * Value of the timer (current value) "TIM" If you set the data display format for a Numeric Display to "16 Bit Decimal" in GP-PRO/PB3, the data will be displayed in BCD. GP-Pro EX displays data in decimal if you set the data type for a Data Display to "16 Bit Dec". Because PLC's handle timers (current value) in BCD, you need to set the data display format to "16 Bit BCD" in GP-Pro EX to display data the same as the ladder software does. Ladder software (BCD) | GP-PRO/PB3 (Data type: Dec) | GP-Pro EX (Data type: Dec) | GP-Pro EX (Data type: BCD) | 10 | 10 | 16 | 10 | 62 | 62 | 98 | 62 | | | | | Warning messages of project conversion | - | If a project file of GP-PRO/PB3 is converted using the Project Converter in the following cases, a warning message will appear. | | Warning Messages | Descriptions | Baudrate which cannot communicate is chosen. It changed into 19200bps which is a default. | This message will appear if you selected the unsupported baudrate in GP-Pro/PB3. | The feature of “Multi Link (n to 1)” is not supported yet. This project has been converted to normal (“1 to 1” or “1 to n”) connection. | This message will appear if the settings for the multi-link connection is set. | | | | Refer to |  | |  | |