RHAA051(Node Name): Out of range devices exist in read devices (Address: (Device Address))
Error Details
The error message [RHAA051(Node Name): Out of range devices exist in read devices (Address: (Device Address))] appeared on the GP3000 screen.
Causes
When more than 2 addresses are set on a Text Display or D-script, etc., the end address may be set out of the address range even though the start address is set within the range.
Actions
1.
Check the addresses used on the screen on which the error occurred. Check if the addresses set on a Text Display or D-script are within the address range.
2.
If the error occurred in all screens, check the addresses set via functions that operate in all screens such as Global D-script and Extended Script.
What is the Global D-script?
・
The Global D-script is one of the programming functions that a touch panel has. With this function, all screens in the project file can be programmed by one D-script.