| 1) | Please match the settings of each unit and I/O Driver Settings. |
| Please follow the steps to confirm the settings. | 1. | Please confirm the unit model in use. | | 2. | Please confirm the communication settings and the settings of S-No. on the main unit. | | Please refer to User Manuals of each unit for more details of the communication settings and the settings of S-No. on the main unit. | | 3. | Please confirm that the communication settings and the type and S-No. of the main unit which is connected are set properly on [I/O Driver Settings]. | | | ・ | Please select [I/O Driver Settings] on [System Settings Window] to set Transmission Speed. | | | | | 4. | Please confirm that S-No. is not duplicated. Number of the occupied stations are depending on each Flex Network Unit. For instance, in case of setting [1] for S-No of the unit which occupied 4 stations, S-No. from 1 to 4 will be occupied. Therefore, S-No. of the next unit will be set with the number after [5]. Otherwise S-No will be duplicated and an error lamp will be turned on. | | | ・ | Numbers of stations of each unit are listed below. | | | Type | Model | No. of Occupied Stations | | I/O Unit | FN-X16TS41 | 1 | | FN-X32TS41 | 2 | | FN-Y16SK41 | 1 | | FN-Y16SC41 | 1 | | FN-XY08TS41 | 1 | | FN-XY16SK41 | 1 | | FN-XY16SC41 | 1 | | FN-XY32SKS41 | 4 | | FN-Y08RL41 | 1 | | Analog Unit | FN-AD02AH41 | 1 | | FN-DA02AH41 | 1 | | FN-AD04AH11 | 4 | | FN-DA04AH11 | 4 | | Single-Axis Positioning Unit | FN-PC10SK41 | 4 | | FN-PC10LD41 | - | | High-Speed Counter Unit | FN-HC10SK41 | 8 | | | |
| 2) | Please run Logic Program. |
| | ・ | Running Logic Program with GP-Pro EX (Editor) → See A) | | ・ | Running Logic Program with the GP main unit → See B) | | A) | With GP-Pro EX (Editor) | | | ・ | Please follow as [System Settings Window] - [Main Unit Settings] - [Logic Settings] tab to select [Run] on [Run at Start Up]. | |  | | | B) | With the GP main unit | | | ・ | Please go to Offline Mode, and open [Main Unit Settings] - [Logic Settings] to select [Run] on [Run at Start up]. | | | |  | | |
| 3) | Please set the wire properly. |
| | 1. | Is Flex Network Cable wired properly? | | | Please refer to User Manuals of each unit for more details of how to set the wire. | | 2. | Please use the cables which Digital Electronics Corporation recommends for Flex Network Cables. | | | ・ | FN-CABLE2010-31-MS(10m) | | | ・ | FN-CABLE2050-31-MS(50m) | | | ・ | FN-CABLE2200-31-MS(200m) | | | |
| 4) | Please set [I/O Settings] ON. |
| | ・ | Setting [I/O Settings] ON with GP-Pro EX (Editor) → See A) | | ・ | Setting [I/O Settings] ON with the GP main unit → See B) | | A) | With GP-Pro EX (Editor) | | | ・ | Please follow as [System Settings Window] - [Main Unit Settings] - [Logic Settings] tab to check on [I/O Settings]. | |  | | | B) | With the GP main unit | | | ・ | Please go to Offline Mode, and open [Main Unit Settings] - [Logic Settings] to set [On] on [Logic Program]. | | | |  | | |