FAQを参照する RHAA035(Node Name): Error has been responded for device write command(Error Code: (Decimal)[(Hex)]) Error Details The error message [RHAA035(Node Name): Error has been responded for device write command (Error Code: (Decimal)[(Hex)]) ] appeared on the GP3000 screen.
Causes 1. The communication settings of the GP unit and those of the device/PLC are not matched. 2. Wiring has problems such as a wrong wire connection or a loose connection. 3. The correct type of the device/PLC is not selected. 4. Addresses out of the range are set.
Actions 1. Check the communication settings of the GP and the device/PLC. If they are not matched, change the communication settings to match them. 2. Rewire if there is a problem in the communication cable wiring or a loose connection. For details of cable diagrams between a GP unit and a device/PLC, please refer to the GP-Pro EX Device/PLC Connection Manual. 3. Change the type of the device/PLC to the one currently connected. 4. Check the address range of the device/PLC in use. Addresses out of the range may be set.
About error codes ・ Error codes are sent from a device/PLC. Please refer to the manual of the device/PLC for the error details.