{"searchBar":{"inputPlaceholder":"キーワードを入力して「検索」ボタンをクリック","searchBtn":"検索","error":"キーワードを入力してください。"}}
{}
{}
FAQを参照する

RHAA008(Driver Name): This machine does not have any Ethernet interface.


Error Details
The error message [RHAA008(Driver Name): This machine does not have any Ethernet interface] appeared on the GP3000 screen.

Causes
You may have transferred a project file with the settings that the GP model was set to GP-3xx0, even though it was GP-3xx1 and you have selected an Ethernet-supporting driver in the GP-Pro EX's Device/PLC settings.

Actions
Check the model of your GP to see if it is an Ethernet-supporting model (GP-3xx0) or not. GP-3xx1L and GP-3xx1S do not support an Ethernet connection. If your GP is an Ethernet-supporting model, select the correct model in the Display Unit settings of the GP-Pro EX. Then transfer the screen data to the GP unit.
Display Settings
NOTE
To check the model of your GP, see the label on the back of the GP unit.

このFAQはお役に立ちましたか?