EtherNet/IP Adapter
--------------------------------------------------------------------------------

V2.11.0.6
---------
 - PSEIS-765:  Update servX to V1.4.0.0  
 - PSEIS-778:  Update to EtherNet/IP Core V2.1.0.6 


V2.11.0.5
---------
 - PSEIS-761:  Communication does not resume after network identity object reset when application controlled startup is configured 
 - PSEIS-762:  [NJ50] UART communication is not working 
 - PSEIS-763:  Stack crashes on Achilles resource test (CIP Connection Exhaustion) 
 - PSEIS-764:  Update to EtherNet/IP Core V2.1.0.5 
 - PSEIS-766:  Network status LED flashes red when class3 connection is established (certification issue) 
 - PSEIS-767:  [DLR] Under certain conditions the device does not handle sign on frames correctly after power up (certification issue) 
 - PSEIS-768:  [QoS, CIP Sync] DSCP values of attribute 2 and 3 are applied automatically without type 0 reset (certification issue) 
 - PSEIS-769:  [CIP Sync] No synchronization with Rockwell device EN2T/A/B/C (certification issue) 
 - PSEIS-770:  Update to PTP V1.2.0.3 


V2.11.0.4
---------
 - PSEIS-755:  [LFW] DLR cannot be disabled 


V2.11.0.3
---------
 - PSEIS-758:  Device sets DSCP values in IP header to 0 after reset type 0 - QuickConnect Only (certification issue) 
 - PSEIS-760:  Update to PTP V1.2.0.2 


V2.11.0.2
---------
 - PSEIS-748:  Reduce jitter of transmitted IO frames 
 - PSEIS-756:  Connection status is not reported correctly in attribute 5 of identity object (extended device status) 
 - PSEIS-757:  Update to EtherNet/IP Core V2.1.0.4 


V2.11.0.1
---------
 - PSEIS-745:  TLR_E_CABLE_DISCONNECT is shown after power up and active link 
 - PSEIS-746:  Configuration change is rejected with TLR_E_IP_ERR_INIT_INVALID_FLAG 
 - PSEIS-747:  Ethernet Link object revision must be 4 in EDS files 


V2.11.0.0
---------
 - PSEIS-673:  Update to rcX V2.1.11.6 
 - PSEIS-676:  [LFW] Boottokens from 2nd stage loader are not evaluated properly 
 - PSEIS-677:  QoS values are not set to proper default values in case older SET_CONFIGURATION packets are used (certification issue) 
 - PSEIS-679:  Increase aging time of MAC address learning table to 30 seconds (certification issue) 
 - PSEIS-681:  Ethernet link is sometimes not established in autoneg mode in case the link parter is configured to use 10MBit/s (certification issue) 
 - PSEIS-682:  Inactivity Timeout value is not set to proper default value in case older SET_CONFIGURATION packets are used (certification issue) 
 - PSEIS-683:  Invalid use of TLR_BOOLEAN in API Header 
 - PSEIS-685:  [LFW] 2nd Stage loader flash boot tokens are not evaluated when being started RAM based 
 - PSEIS-686:  Get Firmware Parameter request returns wrong parameter value 
 - PSEIS-687:  Packet EIP_OBJECT_CONNECTION_CONFIG_IND holds complete forward open data in field abData 
 - PSEIS-723:  [CIP Sync] Pulse length of sync signal needs to be configurable 
 - PSEIS-725:  RCX_HW_HARDWARE_INFO_CNF returns wrong license data 
 - PSEIS-726:  Transmission type is not provided with RCX_GET_DPM_IO_INFO_CNF 
 - PSEIS-730:  xChannelIORead may fail during stack reset 
 - PSEIS-732:  Watchdog time range is not validated 
 - PSEIS-733:  Stack cannot be reconfigured when "duplicate IP address" error occurred (database configuration only) 
 - PSEIS-734:  AP task state remains at watchdog error after channel init 
 - PSEIS-735:  RCX_START_STOP_COMM_REQ does not return RCX_E_INVALID_PARAMETER 
 - PSEIS-737:  MMIO settings is overwritten from 2nd state bootloader 
 - PSEIS-738:  MS / NS LEDs flashing rate is not correct 
 - PSEIS-739:  Update to PTP V1.2.0.1 
 - PSEIS-740:  Update to EtherNet/IP Core V2.1.0.3 


V2.10.5.0
---------
 - PSEIS-715:  Update to EtherNet/IP Core V2.1.0.2 
 - PSEIS-723:  [CIP Sync] Pulse length of sync signal needs to be configurable 
 - PSEIS-724:  Update to PTP V1.2.0.0 
 - PSEIS-725:  RCX_HW_HARDWARE_INFO_CNF returns wrong license data 
 - PSEIS-726:  Transmission type is not provided with RCX_GET_DPM_IO_INFO_CNF 
 - PSEIS-730:  xChannelIORead may fail during stack reset 
 - PSEIS-732:  Watchdog time range is not validated 
 - PSEIS-733:  Stack cannot be reconfigured when "duplicate IP address" error occurred (database configuration only) 
 - PSEIS-734:  AP task state remains at watchdog error after channel init 
 - PSEIS-735:  RCX_START_STOP_COMM_REQ does not return RCX_E_INVALID_PARAMETER 
 - PSEIS-737:  MMIO settings is overwritten from 2nd state bootloader 
 - PSEIS-738:  MS / NS LEDs flashing rate is not correct 


V2.10.4.0
---------
 - PSEIS-681:  Ethernet link is sometimes not established in autoneg mode in case the link parter is configured to use 10MBit/s (certification issue) 
 - PSEIS-682:  Inactivity Timeout value is not set to proper default value in case older SET_CONFIGURATION packets are used (certification issue) 
 - PSEIS-683:  Invalid use of TLR_BOOLEAN in API Header 
 - PSEIS-684:  Update TCP/IP Stack to V2.2.0.4 (certification issue) 
 - PSEIS-685:  [LFW] 2nd Stage loader flash boot tokens are not evaluated when being started RAM based 
 - PSEIS-686:  Get Firmware Parameter request returns wrong parameter value 
 - PSEIS-687:  Packet EIP_OBJECT_CONNECTION_CONFIG_IND holds complete forward open data in field abData 
 - PSEIS-688:  Update to EtherNet/IP Core V2.0.13.0 
 - PSEIS-695:  Stack loses factory default settings after IP address conflict 
 - PSEIS-696:  Start by Application not used when Quick Connect is activated (certification issue) 
 - PSEIS-697:  Update to EtherNet/IP Core V2.0.14.0 


V2.10.3.0
---------
 - PSEIS-677:  QoS values are not set to proper default values in case older SET_CONFIGURATION packets are used (certification issue) 
 - PSEIS-678:  Update TCP/IP Stack to V2.2.0.3 (certification issue) 
 - PSEIS-679:  Increase aging time of MAC address learning table to 30 seconds (certification issue) 
 - PSEIS-680:  Update to EtherNet/IP Core V2.0.12.0 (certification issue) 


V2.10.2.0
---------
 - PSEIS-672:  Update component Ethernet-2-Port Switch to V1.0.9.0 (certification issue) 
 - PSEIS-673:  Update to rcX V2.1.11.6 
 - PSEIS-674:  Update to EtherNet/IP Core V2.0.11.0  
 - PSEIS-676:  [LFW] Boottokens from 2nd stage loader are not evaluated properly 


V2.10.1.0
---------
 - PSEIS-666:  Update to EtherNet/IP Core V2.0.9.0  


V2.10.0.12
----------
 - PSEIS-758:  Device sets DSCP values in IP header to 0 after reset type 0 - QuickConnect Only (certification issue) 


V2.10.0.11
----------
 - PSEIS-729:  Update to EIP Core V2.0.14.2 
 - PSEIS-730:  xChannelIORead may fail during stack reset 


V2.10.0.10
----------
 - PSEIS-714:  Update to EtherNet/IP Core V2.0.14.1 


V2.10.0.9
---------
 - PSEIS-696:  Start by Application not used when Quick Connect is activated (certification issue) 
 - PSEIS-697:  Update to EtherNet/IP Core V2.0.14.0 


V2.10.0.8
---------
 - PSEIS-695:  Stack loses factory default settings after IP address conflict 


V2.10.0.7
---------
 - PSEIS-686:  Get Firmware Parameter request returns wrong parameter value 
 - PSEIS-687:  Packet EIP_OBJECT_CONNECTION_CONFIG_IND holds complete forward open data in field abData 
 - PSEIS-688:  Update to EtherNet/IP Core V2.0.13.0 


V2.10.0.6
---------
 - PSEIS-685:  [LFW] 2nd Stage loader flash boot tokens are not evaluated when being started RAM based 


V2.10.0.5
---------
 - PSEIS-683:  Invalid use of TLR_BOOLEAN in API Header 
 - PSEIS-684:  Update TCP/IP Stack to V2.2.0.4 (certification issue) 


V2.10.0.4
---------
 - PSEIS-681:  Ethernet link is sometimes not established in autoneg mode in case the link parter is configured to use 10MBit/s (certification issue) 
 - PSEIS-682:  Inactivity Timeout value is not set to proper default value in case older SET_CONFIGURATION packets are used (certification issue) 


V2.10.0.3
---------
 - PSEIS-677:  QoS values are not set to proper default values in case older SET_CONFIGURATION packets are used (certification issue) 
 - PSEIS-678:  Update TCP/IP Stack to V2.2.0.3 (certification issue) 
 - PSEIS-679:  Increase aging time of MAC address learning table to 30 seconds (certification issue) 
 - PSEIS-680:  Update to EtherNet/IP Core V2.0.12.0 (certification issue) 


V2.10.0.2
---------
 - PSEIS-672:  Update component Ethernet-2-Port Switch to V1.0.9.0 (certification issue) 
 - PSEIS-673:  Update to rcX V2.1.11.6 
 - PSEIS-674:  Update to EtherNet/IP Core V2.0.11.0  
 - PSEIS-676:  [LFW] Boottokens from 2nd stage loader are not evaluated properly 


V2.10.0.1
---------
 - PSEIS-667:  Update ETH2PS to V1.0.6.1 (certification issue) 
 - PSEIS-669:  Update to EtherNet/IP Core V2.0.10.0 (certification issue) 


V2.10.0.0
---------
 - PSEIS-592:  Update component Ethernet-2-Port Switch to V1.0.6.0 
 - PSEIS-609:  Support the Encapsulation Inactivity Timer value in the set configuration packet 
 - PSEIS-610:  Support TCP/IP Interface object revision 4 in EDS files 
 - PSEIS-615:  Update to TCP/IP Stack V2.1.32.0 
 - PSEIS-619:  comX51: Serial diagnostic is not available 
 - PSEIS-620:  Update to EtherNet/IP Core V2.0.7.0  
 - PSEIS-624:  [cifX, comX, netJACK, NXO] CIP Sync is not available on some targets 
 - PSEIS-625:  [netX51, comX51, netJACK51] Web server is not accessible 
 - PSEIS-627:  Address conflict LED state is overwritten by closing class 3 connection (certification issue) 
 - PSEIS-628:  Update to PTP V1.0.4.0 
 - PSEIS-632:  NXIO 50 does not start 
 - PSEIS-633:  MS/NS LEDs signal duplicate IP address although IP address was successfully obtained after temporary conflict - DHCP/BOOTP only (certification issue) 


V2.9.8.0
--------
 - PSEIS-632:  NXIO 50 does not start 
 - PSEIS-633:  MS/NS LEDs signal duplicate IP address although IP address was successfully obtained after temporary conflict - DHCP/BOOTP only (certification issue) 


V2.9.7.0
--------
 - PSEIS-624:  [cifX, comX, netJACK, NXO] CIP Sync is not available on some targets 
 - PSEIS-625:  [netX51, comX51, netJACK51] Web server is not accessible 
 - PSEIS-627:  Address conflict LED state is overwritten by closing class 3 connection (certification issue) 
 - PSEIS-628:  Update to PTP V1.0.4.0 


V2.9.6.0
--------
 - PSEIS-619:  comX51: Serial diagnostic is not available 
 - PSEIS-620:  Update to EtherNet/IP Core V2.0.7.0  


V2.9.5.0
--------
 - PSEIS-592:  Update component Ethernet-2-Port Switch to V1.0.6.0 
 - PSEIS-609:  Support the Encapsulation Inactivity Timer value in the set configuration packet 
 - PSEIS-610:  Support TCP/IP Interface object revision 4 in EDS files 
 - PSEIS-615:  Update to TCP/IP Stack V2.1.32.0 


V2.9.4.1
--------
 - PSEIS-541:  Sometimes DPM Ready Flag not set after performing channel Init 


V2.9.4.0
--------
 - PSEIS-538:  Updated to EtherNet/IP Core V2.0.5.0 
 - PSEIS-539:  Updated to PTP V1.0.3.0 


V2.9.3.0
--------
 - PSEIS-336:  [NetJACK] "Device Type" and "Device Name" remain "Undefined" in netIdent 
 - PSEIS-352:  EIP_OBJECT_RESET_REQ can't reset stack after WDT event 
 - PSEIS-458:  The DPM Error Counter is not cleared on Channel Init, when the stack is configured by INIBATCH.NXD. 
 - PSEIS-466:  NXIO 100 operates at 10 Mbit/s only 
 - PSEIS-530:  Startup time is delayed unnecessarily when SET_CONFIGURATION is used for configuration 
 - PSEIS-531:  update to rcX v2.1.10.0 
 - PSEIS-534:  LED startup test sequence might be skipped if host application configures the stack very early after it signals to be ready. 
 - PSEIS-535:  Updated to EtherNet/IP Core V2.0.4.0 


V2.9.2.2
--------
 - PSEIS-685:  [LFW] 2nd Stage loader flash boot tokens are not evaluated when being started RAM based 


V2.9.2.1
--------
 - PSEIS-531:  update to rcX v2.1.10.0 


V2.9.2.0
--------
 - PSEIS-473:  No meaningful error code returned when no MAC address available 
 - PSEIS-492:  Stack does not send extended status value that is put into ulERC in the packet EIP_OBJECT_CL3_SERVICE_RES (0x1A3F) 
 - PSEIS-523:  Wrong DLR Object version in EDS files 
 - PSEIS-524:  Add section [TCP/IP Interface Class] in EDS files 
 - PSEIS-525:  Update to rcX V2.1.9.0 
 - PSEIS-526:  Feature: Support new parameter "Admin State" (Ethernet Link Object) in packet EIP_APS_SET_CONFIGURATION_PARAMETERS_REQ (0x00003612) 
 - PSEIS-527:  Update to Ethernet 2 Port Switch V1.0.3.0 
 - PSEIS-528:  Update to PTP V1.0.2.0 
 - PSEIS-529:  Update to EtherNet/IP Core V2.0.2.0 


V2.9.1.0
--------
 - PSEIS-352:  EIP_OBJECT_RESET_REQ can't reset stack after WDT event 
 - PSEIS-372:  Channel Init fails if no link is available 
 - PSEIS-416:  Stack uses vendor specific error 0x320 when addressing assemblies incorrectly in an incoming ForwardOpen 
 - PSEIS-423:  TCP/IP Interface Object Attr 4: Path to Physical Link invalid for multi-port device 
 - PSEIS-425:  Quick Connect  only: Stack does not properly close TCP connections upon receipt of Forward_Close 
 - PSEIS-448:  LOM only: If FwdOpen forwarding is used, stack crashes during internal handling of FwdOpen message 
 - PSEIS-450:  AP-Task must not configure PHYs upon receiption of TCP Set_Config packet  (0x200) in case Quick Connect is enabled 
 - PSEIS-451:  Setting of Ethernet Link Attribute 6 is not rejected when Quick Connect is active 
 - PSEIS-460:  When using BOOTP/DHCP and an address conflict occurres on startup, the device tries to obtain a new address in an endless loop 
 - PSEIS-464:  Identity Object reports "No I/O connection established" although an Exclusive Owner connection is running 
 - PSEIS-466:  NXIO 100 operates at 10 Mbit/s only 
 - PSEIS-467:  IP Header field "router alert" missing in IGMPv2 telegrams 
 - PSEIS-470:  Device drops frames when used in a Device Level Ring topology (netx100) 
 - PSEIS-478:  Gateway MAC address is not used for unicast I/O frames going to devices that are not in the same subnet 
 - PSEIS-479:  Time To Live (TTL) value in IP header of I/O frames is not correct 
 - PSEIS-480:  Stack does not reject multicast connection to  a device that is located in another subnet, if the TTL value is <= 1. 
 - PSEIS-490:  Device drops frames when used in a Device Level Ring topology (netx50) 
 - PSEIS-497:  Feature: Add support for target comX51 
 - PSEIS-506:  AP task stays in watchdog error after channel init. 
 - PSEIS-508:  NJ50: Wrong DPM size in system information. 
 - PSEIS-510:  Feature: Support CIP TCP/IP Interface Object V3 (class 0xF5) 
 - PSEIS-511:  Feature: Support CIP DLR Object V3 (class 0x47) 
 - PSEIS-512:  Stack fails at Connection Manager Test (ForwardOpen Test) of the Conformance Test Tool CT11 
 - PSEIS-514:  Update to rcX V2.1.7.0 
 - PSEIS-515:  I/O connections cannot be established when using parameter flag EIP_OBJECT_PRM_FWRD_OPEN_CLOSE_FORWARDING  
 - PSEIS-518:  Duplicate data packets of class 3 transports are not handled properly 
 - PSEIS-519:  Packet EIP_OBJECT_CL3_SERVICE_IND: Missing reference value to service related class 3 connection. 
 - PSEIS-521:  Update to new standard 2 Port Switch V1.0.2.0 
 - PSEIS-522:  Use EtherNet/IP Core component V2.0.1.0 


V2.8.3.0
--------
 - PSEIS-424:  COMX Firmware: wrong device class 


V2.8.2.0
--------
 - PSEIS-421:  CIP Sync Support for netX100 
 - PSEIS-422:  Stack reports wrong interface control value (class 0xF5 attribute 3) for a short time after applying the IP address 


V2.7.24.0
---------
 - PSEIS-550:  DLR Sign-On response frame format is incorect in networks with more than 4 ring participant 


V2.7.23.0
---------
 - PSEIS-547:  Gateway MAC address is not used for unicast I/O frames going to devices that are not in the same subnet 


V2.7.22.0
---------
 - PSEIS-542:  Time To Live (TTL) value in IP header of I/O frames is not correct 


V2.7.21.0
---------
 - PSEIS-534:  LED startup test sequence might be skipped if host application configures the stack very early after it signals to be ready. 


V2.7.20.0
---------
 - PSEIS-533:  [netX51, netJack51, comX51] Firmware fail to start 


V2.7.19.0
---------
 - PSEIS-531:  update to rcX v2.1.10.0 


V2.7.18.0
---------
 - PSEIS-530:  Startup time is delayed unnecessarily when SET_CONFIGURATION is used for configuration 


V2.7.17.0
---------
 - PSEIS-515:  I/O connections cannot be established when using parameter flag EIP_OBJECT_PRM_FWRD_OPEN_CLOSE_FORWARDING  


V2.7.16.0
---------
 - PSEIS-517:  Packet EIP_OBJECT_CL3_SERVICE_IND: Missing reference value to service related class 3 connection. 


V2.7.15.0
---------
 - PSEIS-513:  Duplicate data packets of class 3 transports are not handled properly 


V2.7.14.0
---------
 - PSEIS-510:  Feature: Support CIP TCP/IP Interface Object V3 (class 0xF5) 
 - PSEIS-511:  Feature: Support CIP DLR Object V3 (class 0x47) 
 - PSEIS-512:  Stack fails at Connection Manager Test (ForwardOpen Test) of the Conformance Test Tool CT11 


V2.7.13.0
---------
 - PSEIS-501:  [comX 51] Web server does not work 
 - PSEIS-504:  [netJACK 51] COM port does not work 
 - PSEIS-505:  [netJACK 51] Web server does not work 


V2.6.12.0
---------
 - PSEIS-397:  Port of servX should be setable 