Wiring of Serial Interface and Each Switch
|
Serial interface connector, Emergency stop switch/Enabling switch connector, Key switch connector |
|
|---|---|
|
Connector |
Plug-in
connector (plug) |
|
Cord cross-section*1 |
0.14...1.5 mm2 (AWG 30...16) |
|
Conductor type |
Solid or
stranded wire |
|
Conductor length (insulation stripping length) |
10 mm (0.39 in) |
|
Compatible terminal types |
Plastic collar ferrule: 0.14...1 mm2, DIN 46228-4 compliant |
|
Recommended screwdriver |
Flat-head screwdriver (size of blade: 0.4 x 2.5 mm), DIN5264 compliant |
*1 Thick wires are recommended.
- Check the pin assignment of each connector and insert the
wire all the way into the insertion slot for each wire. For pin assignments,
refer to Interface Specifications of Wired Adapter.NOTE: To remove the wire, press the release button with your finger or a screwdriver and pull out the wire.
- After all the required wires are plugged in, insert the connectors into the adapter and secure with the connector fixing screw. The necessary torque is 0.15 to 0.2 N•m (1.33 to 1.77 lb-in).