GPH6000-MM01-EN.00

Emergency Stop Switch

WARNING
UNINTENDED EQUIPMENT OPERATION
  • The suitability of using the emergency stop switch should be determined by a risk assessment of the system.
  • Before operating this product on the actual system, as well as periodically, check its operation (proof test).
  • Perform testing under controlled conditions. For example, when testing the emergency stop switch, the operator must be outside the working range of the moving machine.
  • Unlock after confirming safety.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTICE
EQUIPMENT DAMAGE
Do not expose the switch to excessive shock or vibration.
Failure to follow these instructions can result in equipment damage.

This product has an illuminated push button switch with two break contacts (b-contact, normally closed) as the emergency stop switch. While the emergency stop switch is showing red, it indicates that the emergency stop function is able to run.

NOTE:
  • The emergency stop switch lights up when the product is powered on.

  • For the safety function parameters of this switch, refer to Safety Parameters.

The continuity state when the switch is pressed is as follows:

Signal name

Switch not pressed

Switch pressed

EMG1

1 (ON)

0 (OFF)

EMG2

1 (ON)

0 (OFF)

To unlock the switch, pull it up or turn it in the direction of the arrow.