Error Code  | 
		Error Message  | 
		Solution  | 
	
RHxx128  | 
		Error During Initialization of Interface Module  | 
		The unit may be faulty. Check the module.  | 
	
RHxx129  | 
		Illegal Initialization Parameter  | 
		Decrease the size of input or output area in the device/PLC settings and the unit settings.  | 
	
RHxx130  | 
		Incorrect Interface Module Detected  | 
		Connect the correct module.  | 
	
RHxx131  | 
		Network Communication Error, LED Status: [0x0*]*1  | 
		Check the settings of cables, communication speed, input/output sizes, and master (scanner). Please check the LED status for details.  | 
	
*1 Using the LED status and LED display, you can check the following states.
  
LED Status  | 
		Network LED  | 
		Module LED  | 
		Description  | 
	
0x00 to 0x04  | 
		Does not light up  | 
		Flashing (Green)  | 
		Indicates any of the following conditions: No electricity is supplied on the network cable, a cable is not connected or the configuration (including settings) has not been set.  | 
	
0x04  | 
		Light is off  | 
		Lit (Green)  | 
		Indicates any of the following conditions: No electricity is supplied on the network cable, a cable is not connected or the baud rate has not been properly set.  | 
	
0x04 to 0x05  | 
		Flashing (Green)  | 
		Lit (Green)  | 
		Indicates any of the following conditions: This slave has not been set on the network or the configuration has not been properly set. Confirm the slave number.  | 
	
0x05  | 
		Lit (Green)  | 
		Lit (Green)  | 
		The master is in stop mode.  | 
	
0x06  | 
		Lit (Red)  | 
		Lit (Green)  | 
		Check the network settings. The baud rate setting is incorrect or, some settings may be overlapping (for example, slave setting).  |