The analog output module defines output range, customizable value, and fallback value using configuration object.
| Channel | Object (Hex) | Sub index | Description | Parameter | 
| CH1 | 2200 | n | Data Format | 0: Disable 2: Current (4 to 20mA) 3: Voltage (0 to 10V) | 
| 2201 | n | Data range | 0: Fixed 1: User setting | |
| 2202 | n | Lower limit | Lowest value | |
| 2203 | n | Upper limit | Highest value | |
| 6411 | n | Written value | Output | |
| 6443 | n | Fallback mode | 0: Retentive State 1: Fallback | |
| 6444 | n | Fallback Value (when 6443h = 1) | Fallback Value |