Recovery Mode

Overview

When a display unit fails to accept the project in a transfer operation, follow the steps below to enter recovery mode and transfer the project again. If a problem occurs during a project transfer operation, the system automatically enters recovery mode.

Important:

Recovery via Touch

Note:

  1. Turn on the display unit.
  2. Touch and hold the bottom-left corner or bottom-right corner (within an 80 pixel area) of the display until a dialog box appears.
  3. Note:

    • When the project is set up in portrait mode, the corners of the touch areas for entering recovery mode are as follows:
      • When display is rotated clockwise

      • When display is rotated counter-clockwise
    • For information on rotating display units, refer to [Orientation] in the following
      Target Settings.

    The dialog box displays the question, "Do you want to enter recovery mode?"

  4. Click [Yes] to enter recovery mode.
  5. Transfer the project. Depending on your transfer method, the following setup may be required.
Setting Description
[Ethernet Download] [Enable]
[IPsec] Touch [IPsec], select [Enable] and set the [Preshared Key].
[Ethernet] Displays the [IP Address], [Subnet Mask], and [Default Gateway]. If you are using a model where these settings are not visible, touch [Ethernet] to view.
Setting Description
[Ethernet Download] [Enable]
[IPsec] Touch [IPsec], select [Disable].
[Ethernet] Displays the [IP Address], [Subnet Mask], and [Default Gateway]. If you are using a model where these settings are not visible, touch [Ethernet] to view.

Recovery via Application

You can use the following recovery method on SP5000 Series Open Box, IPC Series, and PC/AT display units.

Important: Exit other applications before performing recovery. If project transfer fails during recovery, the operating system will restart without confirmation.

  1. If BLUE Runtime is running, exit the application.
  2. From the Windows Start menu, start [BLUE Runtime Recovery Mode].

    Note:

    • When the User Account Control dialog box for running TransferService.exe as an administrator is displayed, click [Yes].
    • If [BLUE Runtime Recovery Mode] is not available in the Start menu, from the folder below right-click TransferService.exe and from the shortcut menu select [Run as administrator], to run the application with administrator rights. Close the folder after BLUE Runtime Recovery Mode starts up. If you run transfer while the folder is open, an error will occur.

    C:\Program Files\Pro-face\BLUE Runtime\RTPrimaryBoot\TransferService.exe

  3. Transfer the project. Depending on your transfer method, the following setup may be required.