Error Code

MP Series

Error Code

Description

0x90

Transfer error

0x92

Illegal parameter

0x96

Register No. over

0x9C

File is modified

0x9D

Data access error

 

Inverter Series

Error Code

Description

0x01

Function code error

0x02

Invalid register number error

0x03

Invalid quantity error

0x21

Data setting error

0x22

Write mode error

0x23

Main circuit undervoltage (UV) error during write

0x24

Write error during processing of constants

 

Servo Series

Error Code

Description

0x01

Function Code Error

  • Unsupported function code or sub function code in use.

0x02

Faulty Register Number

  • Accessing register number that is not registered.

0x03

Faulty Quantity

  • The number of read or write data for reading is not between one and the maximum quantity (as defined per model).

  • In write mode, the number of data in the message is not the specified quantity.

0x30

Faulty Register Number (High Level)

  • Accessing register number that is not registered.

0x31

Access Limit Error

  • Access to the specified register is not permitted.

0x32

Outside Setting Range Error

  • The write data value is outside the maximum and minimum limit.

0x33

Data Matching Error

  • Tried to access only a portion of registers in the multiple register unit.

  • Tried to access multiple registers that exceed the register group.

0x34

Condition Error

  • Command message content cannot be processed due to the condition defined by the register.

0x35

Process Conflict Error

  • Cannot be processed due to priority issues with other channels.

0x36

Axis number error (Σ-7W/Σ-7C series only)

  • The extended address is using an axis number that is not available.

 

I/O (M-System)

Error Code

Description

0x01

Function Code Error

  • Unsupported function code or sub function code in use.

0x03

Faulty Quantity

  • The data count in read or write operations is outside the allowed range (1 to the maximum, as defined per model).

  • In write mode, the data count in the message does not match the specified quantity.

0x04

Data Type Error

  • Not supported by the defined mode or data type.

0x09

Process Conflict Error

  • Cannot process due to priority issues with other channels.

0x81

Protocol ID Setting Error

  • When running a vendor specific command, the protocol ID did not match the I/O.

0x82

Data Length Setting Error

  • When running a vendor specific command, the data length setting for the vendor special area does not match the I/O.

0x83

Vendor Special Area Error

  • When running a vendor specific command, a vendor special error occurred in the vendor special area.

Example:

 Error code = 0x83, and the vendor special error code = 0x01, it is displayed 83,01.

Vendor special error code

Error Code

Description

0x01

Model code error

  • The specified model code does not match the I/O.

0x02

Specified channel error

  • The I/O does not support the specified channel.

0x03

Setting command error

  • The I/O does not support the setting command.

0x04

Setting command data error

  • Error in the setting command data.

  • If the error code is 0x83, it is displayed together with the vendor special error code.

 

I/O (Azbil)

Error Code

Description

0x01

Function Code Error

  • Unsupported function code or sub function code in use.

0x02

Memory Address Error

  • Memory address you tried to access is not in the memory address range.

0x03

Faulty Quantity

  • The data count in read or write operations is outside the allowed range (1 to the maximum, as defined per model).

0x04

Data Type Error

  • Not supported by the defined mode or data type.

  • Not supported by the protocol ID or device code.

0x81

Protocol ID Setting Error

  • When running a vendor specific command, the protocol ID did not match the I/O.

0x82

Data Length Setting Error

  • When running a vendor specific command, the data length setting for the vendor special area does not match the I/O.

0x83

Vendor Special Area Error

  • When running a vendor specific command, a vendor special error occurred in the vendor special area.

Vendor special error code

Error Code

Description

0x01

Azbil protocol ID setting error

  • The specified Azbil protocol ID is not supported by the I/O.

Example:

 Error code = 0x83, vendor special error code = 0x81, and Modbus error code = 0x01, it is displayed 83,81,01.

Vendor special error code

Error Code

Description

0x81

MODBUS RTU abnormal response

  • Received a Modbus error. For more information, check the Modbus error code table.

Modbus error code

Error Code

Description

0x01

Illegal function

  • Unsupported function code in use

  • Connected to unsupported the I/O

0x02

Illegal data address

  • Data address error (area where access is prohibited)

0x03

Illegal data

  • Write out-of-range value

  • Equipment related, write-protected and read prohibited

0x13

Write mode error

  • If the error code is 0x83, and the vendor special error code is 0x01, it is displayed 83,01.
  • If the error code is 0x83, and the vendor special error code is 0x81, it is displayed together with the Modbus error.

 

Stepping (ORIENTAL MOTOR)

Error Code

Description

0x01

Function Code Error

  • Unsupported function code or sub function code in use.

0x02

Faulty Register Number

  • Accessing register number that is not registered.

0x03

Faulty Quantity

  • The number of read or write data for reading is not between one and the maximum quantity (as defined per model).

  • In write mode, the number of data in the message is not the specified quantity.

0x04

Data Type Error

  • Not supported by the defined mode or data type.

0x05

Access Limit Error

  • Access to the specified register is not permitted.

0x06

Outside Setting Range Error

  • The write data value is outside the maximum and minimum limit.

0x07

Data Matching Error

  • Tried to access only a portion of memory in the multiple register unit.

  • Tried to access multiple registers that exceed the register group.

0x08

Condition Error

  • Command message content cannot be processed due to the condition defined by the register.

0x09

Process Conflict Error

  • Cannot be processed due to priority issues with other channels.