Display (Connection Port) |
Cable |
Remarks |
|
|---|---|---|---|
GP-4116 (COM1) |
User-created cable |
Cable length: 50m or less |
|
SP5000 (COM1/2) |
RS-422 terminal block conversion adapter by Pro-face PFXZCBADTM1 + |
Cable length: 50m or less |
|
COM port conversion adapter by Pro-face CA3-ADPCOM-01 + Terminal block conversion adapter by Pro-face CA3-ADPTRM-01 + User-created cable |
|||
User-created cable |
|||
|
PS5000 |
User-created cable |
Cable length: 50m or less |
|

DANGER
ELECTRIC SHOCK
Ensure that the ground connection for each component of interconnected equipment is reliably connected to the same ground potential (within 100 ohms) prior to connecting the equipment.
WARNING
UNINTENDED EQUIPMENT OPERATION
Use shielded twisted-pair cables.
Connect the cable shields, then connect the cable to a single-point ground on the Display side.